The ESP Fireline 2 Zone conventional fire alarm panel.
- 2 programmable zones
- Active end of line monitoring and head removal
- 30 fire detectors per zone
- Unlimited number of call points per zone
- Integral sound alarm button
- 'Class change' facility
- Enable/disable security key
- One man walk test facility
- Volt free fire change over relay
- Volt free fault change over relay
- Individual sounder circuit fault ID
- Individual zone/sounder isolate
- CE certified to EN54 P2/4
- Requires only 1x12v battery
- MAG2P - ABS casing
Technical
Max Detectors per Zone |
30 |
Thresholds for Zone Conditions |
0 - 2 mA (Fault condition) 2 - 6 mA (Normal condition) 6 - 110 mA (Fire condition) 110 mA - Short (Fault condition) |
Mains Supply |
230 VAC ± 10% |
Standby Supply |
1 x 7ah 12V S.L.A. Battery |
Sounder 1 |
24V (max 300mA fused) |
Sounder 2 |
24V (max 300mA fused) |
Fault/Fire Relay |
Volt free 500mA @ 24V (max load) |
Auxiliary Output |
24VDC (300mA fused) |
Working Temperature |
0 to 40ºC |
Storage Temperature |
-20 to 60ºC |
Humidity |
0 - 95% |
Dimensions MAG2P |
340 x 290 x 100mm |
Dimensions MAG2 |
200 x 290 x 80mm |
Weight |
MAG2P - 2.1Kg MAG2 - 2.7Kg |
Documents
Full Datasheet