An Apollo XP95 Multisensor Detector (55000-885APO).
- Fully compatible with C-TEC's XFP & ZFP XP95/Discovery Addressable Fire Panels.
- Combines an optical smoke sensor and thermistor temperature sensor.
- Responds well to a wide range of fires.
- Well suited for environments such as hotel bedrooms.
- Red LED illuminates when the detector is in alarm.
- Certified to EN54-7 by the LPCB.
- Requires a 45681-210APO standard base or 45681-242APO low power relay base.
- 'Xpert' card addressed for speedy installation.
Technical
Approvals/certifications |
Certified to EN54-7 by the LPCB |
Compatibility |
Compatible with C-TEC's XFP/ZFP XP95/Discovery Addressable Fire Panels |
Application/operation |
Combines inputs from optical smoke and heat sensors and processes them using a sophisticated algorithm. Designed to be sensitive to a wide range of fires. Provides a good response to overheating/thermal combustion and to flaming fires with high heat. |
Application temperature |
TBC |
Static response temperature |
TBC |
Supply wiring |
2-wire, polarity insensitive |
Supply/operating voltage |
17 to 28V DC |
Quiescent current |
500µA average; 750µA peak |
Alarm current |
2mA (LED illuminated) |
Indicators |
Clear LED emitting red light when in alarm |
Connections |
L1&L2 supply in/out; +R remote LED +Ve connection; -R remote LED -Ve connection. (4mA remote LED current @ 5V measured across remote load). |
Product dimensions (mm) |
100mm diameter x 50 mm H (not in base). 58mm height when in base |
Construction & finish |
White polycarbonate V.O rated rated to UL94. Stainless steel terminals |
IP Rating |
IP43 |
Weight |
105g (not in base); 160g (in base) |
Operating conditions/temperature |
-20ºC to +60ºC |
Notes |
Requires a BF308XP standard base or BF308XPR low power relay base. 1mA power up surge current for 0.3 seconds |