An Apollo XP95 Optical Smoke Detector (55000-600APO).
- Fully compatible with C-TEC's XFP & ZFP XP95/Discovery Addressable Fire Panels.
- Works using the light scatter principle.
- Responds well to slow-burning, smouldering fires.
- Well-suited for bedrooms and escape routes.
- Red LED illuminates when the detector is in alarm.
- Certified to EN54-7 by the LPCB.
- Requires a 45681-210APO standard base or 45681-242APO low power relay base.
- 'Xpert' card addressed for speedy installation.
Technical
Approvals/certifications |
Certified to EN54-7 by the LPCB |
Compatibility |
Compatible with C-TEC's XFP/ZFP XP95/Discovery Addressable Fire Panels |
Application/operation |
Generates an alarm when it detects a pre-set threshold of smoke penetration in its smoke chamber. Provides a very good response to overheating/thermal combustion and a good response to smouldering/glowing/flaming combustion & flaming with high heat. |
Application temperature |
N/A |
Sensitivity |
Nominal alarm threshold of 2.4% light grey smoke obscuration per metre |
Supply wiring |
2-wire, polarity insensitive |
Supply/operating voltage |
17 to 28V DC |
Quiescent current |
340µA average; 600µA peak |
Alarm current |
2mA (LED illuminated) |
Indicators |
Clear LED emitting red light when in alarm |
Connections |
L1&L2 supply in/out; +R remote LED +Ve connection; -R remote LED -Ve connection. (4mA remote LED current @ 5V measured across remote load). |
Product dimensions (mm) |
100mm diameter x 42 mm H (not in base). 50mm height when in base |
Construction & finish |
White polycarbonate V.O rated rated to UL94. Stainless steel terminals |
IP Rating |
IP43 |
Weight |
105g (not in base); 157g (in base) |
Operating conditions/temperature |
-20ºC to +60ºC |
Notes |
Requires a BF308XP standard base or BF308XPR low power relay base. 1mA power up surge current for 0.3 seconds |